Installation ManualFOR MODELS:VENMAR 1.3 HE, 1.8 HE & 2.6 HEVENMAR 3055 COMPACT & 5585 COMPACTvänEE 1000 HE, 2000 HE & 3000 HE04435 rev. D
104. Typical Installations4.1 FULLY DUCTED SYSTEM4.2 EXHAUST DUCTED SYSTEM(SOURCEPOINTVENTILATION)(Primarily for homes with radiant hot water or elect
115. InstallationFigure 8• Inspect the exterior of the unit for shipping damage. Ensure that there is no damage to the door, door latches, door hinges
125. Installation (cont’d)5.3 CALCULATING DUCT SIZE (CONT’D)VI00025.3.1 Example for calculation:Problem: My installation requires two exhaust register
5.4 INSTALLING DUCTWORK AND REGISTERS (CONT’D)5.4.2 Exhaust Ducted System (Source Point Ventilation) (see illustration, section 4.2)Stale air exhaust
5.4 INSTALLING DUCTWORK AND REGISTERS (CONT’D)There are two methods (Figures 13 and 14) for connecting the unit to the furnace:Method 1: return-supply
155. Installation (cont’d)5.5.1 For models Venmar 3055 Compact, 5585 Compact, vänEE 1000 HE, vänEE 2000 HE, Venmar 1.3 HE and Venmar 1.8 HEUse the fol
5. Installation (cont’d)5.6 INSTALLING EXTERIOR HOODSChoose an appropriate location for installing the exterior hoods:• At a distance of at least 6 fe
175.7 CONNECTING THE DRAIN5. Installation (cont’d)Make a water trap loop in the tube to prevent the unit from drawing unpleasantodors from the drain s
4- Connect the wires to the main control (see figure beside.)5- Reinstall cover plate and buttons.3- Install the wall control at approximately 60 inch
6.5 FURNACE INTERLOCK TYPESThe TII (Timed Intermittent Interlock) function consists in 2 modes: the standard mode and the special mode. Dependingon th
Table of contents21. Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
207. Wiring DiagramCOLOR CODEBKBLBNGGYNCORWYBLACKBLUEBROWNGREENGREYNO CONNECTIONORANGEREDWHITEYELLOWLINE VOLTAGELOW VOLTAGEAND FIELD WIREDAMPER MOTOR
8. Air Flow Balancing• A magnehelic gauge capable of measuring 0 to 0.25 inches water gauge (0 to 62.5 Pa) and 2 plastic tubes.• Two flow collars (the
8. Air Flow Balancing (cont’d)4. Move tubing to the other side of the unit (location B in figure on page 21) and note reading. Adjust the fresh air ba
10. TroubleshootingNOTE: Inspect the unit before proceeding with these steps.23Problems Possible causes You should try this1. The error code E1 is • T
Problems Possible causes You should try this7. The wall control • TBI mode is activated. •If the outside temperature is below -15°C (5°F), then the T
3These are the two most common methods used to evaluate the ventilation needs of a house:CSA F326:• High speed: 10 cfm per room20 cfm for the master b
42.Service2.1 3D DRAWING FOR VENMAR 1.3 HE, VENMAR 3055 COMPACT, VENMAR 5585 COMPACT AND VÄNEE 1000 HE215667891011121314151617251819198212324262728293
52.Service (cont’d)2.2 PARTS ORDERING CHART FOR VENMAR 1.3 HE,VENMAR 3055 COMPACT, VENMAR 5585 COMPACT AND VÄNEE 1000 HENo Description Venmar Venmar V
62.3 3D DRAWING FOR VENMAR 1.8 HE, VENMAR 2.6 HE, VÄNEE 2000 HE AND VÄNEE 3000 HEVL0006239101114151617188719456121313181762.Service (cont’d)
72.4 PARTS ORDERING CHART FOR VENMAR 1.8 HE,VENMAR 2.6 HE, VÄNEE 2000 HE AND VÄNEE 3000 HE2.Service (cont’d)No Description Venmar Venmar vänEE vänEE1.
3. Technical DataThe direction of the air flow is indicated in each of the following diagrams (Figures 1 and 2). Please note that the stale air never
3.0 Technical Data (cont’d)3.2 DIMENSIONS21"(53.3 cm)18½"(47 cm)27"(68.6 cm)VK0020A6"Ø 6"Ø6"Ø6"ØModel number: Venma