Venmar HEPA 4000 Spécifications

Naviguer en ligne ou télécharger Spécifications pour Pompes à chaleur Venmar HEPA 4000. Venmar HEPA 4000 Specifications Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 61
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
VHC-72
Semi-custom Commercial Energy Recovery Ventilator
Installation, Operation and Maintenance Instructions Manual
Capacity: 5,000 to 8,000 cfm
Model: VHC-72
©2012 Venmar CES
IMPORTANT
The use of this appendix is specifically intended for a
qualified installation and service agency. A qualified in-
stallation and service agency must perform all installation
and service of these appliances.
FOR YOUR SAFETY
What to do if you smell gas:
1. Open windows if appliance is indoors.
2. Do not touch electrical switches or use any phone in
the building.
3. Extinguish any open flame.
4. Leave the building immediately.
5. Immediately call Gas Supplier.
!
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause injury or death. Read the instal-
lation, operation and maintenance instructions thor-
oughly before installing or servicing this equipment.
Vue de la page 0
1 2 3 4 5 6 ... 60 61

Résumé du contenu

Page 1 - Model: VHC-72

VHC-72Semi-custom Commercial Energy Recovery VentilatorInstallation, Operation and Maintenance Instructions ManualCapacity: 5,000 to 8,000 cfmModel: V

Page 2 - Table of Contents

Coil or WSHP Piping ConnectionsConnections to the unit coil or WSHP system is by oth-ers. External supply and return piping design and all other safet

Page 3 - Nomenclature

Gas ConnectionsRefer to Appendix D for gas-fired furnace module installa-tion and maintenance information.Start-upPre Start-up ChecklistBefore requesti

Page 4 - Recommended Spare Parts

Start-up ProcedureTo ensure proper operation of each unit qualified person-nel should perform the start-up and complete the checklist below and the sta

Page 5 - Unit Application Limitations

Airflow BalancingFor proper performance the unit must operate at the spec-ified supply and exhaust flow rates. Unit fan speed(s) and damper positions are

Page 6 - Unit Location Requirements

MaintenancePlease see the mechanical drawings for service clearance dimensions. See Appendix H for troubleshooting and ad-ditional service and mainten

Page 7 - Roofcurbs Supplied by Others

FansFan wheels and housings should be checked for dirt buildup. If the forward curved exhaust fan is dirty, it will be necessary to remove the blower

Page 8 - Hood Installation

Plenum Supply or Exhaust Fan and MotorTo remove plenum fan and motor disconnect the four-wire electrical cable from the motor junction box. Remove the

Page 9 - Electrical Connections

4. After removing the mounting bolts, slide the motor pedestal to the point where the motor lifting ring is exposed enough to use. If a mechanical de

Page 10 - Condensate Drain Trap

12. Reconnect the four-wire electrical cable from the motor junction box. Before operation, start the motor slowly to ensure the fan rotation is corr

Page 11 - Pre Start-up Checklist

5. To make adjustment, loosen (do not remove) all the cone retaining fasteners.6. Using a rubber mallet, gently tap around the cone until desired cl

Page 12 - Start-up Procedure

Table of ContentsRecommended Spare Parts ...

Page 13 - Airflow Balancing

Enthalpy WheelThe opposing airflow pattern through the enthalpy wheel allows for self-cleaning and if the air filters on both air-streams are properly m

Page 14 - Maintenance

Testing and Replacement of the Damper ActuatorAfter disconnecting the power from the unit, determine if the actuator is defective. Disconnect the 24 v

Page 15 - WARNING

Appendix A: Hood InstallationExhaust air dischargehood with birdscreenOutdoor air intakehood with birdscreenIMPORTANT1. Outdoor air intake and exhaus

Page 16 - 1-1/16” to 1¼“ 167

Appendix B: Rigging and Lifting DetailsCAUTION1. Rigging and lifting units without using all lifting lugs will compromise the structural integrity of

Page 17

Appendix C: Water Source Heat Pump (WSHP) Water Line Piping Requirements and OptionsWater Supply and Return Piping RequirementsRecommended and requir

Page 18 - Fan Wheel/Cone Alignment

tion, temperature and pressure limits of the optional com-ponents are provided below.Strainer with Blowdown ValveThe strainer with blowdown valve is a

Page 19

Flow EquationUS gpm = Cv x √∆P/SGWhere:Cv is the flow coefficient for the valve ∆P is the fluid pressure drop across the valve in psi SG is the specific g

Page 20 - Enthalpy Wheel

Appendix D: Gas-fired Furnace Module Installation and MaintenanceThe furnace covered by this appendix is a component of a “Listed” product, subject to

Page 21 - System Operation Check

Outdoor InstallationAir for CombustionThe furnace is power vented with a combustion air draft inducer/blower and needs an ample supply of air for prop

Page 22 - Appendix A: Hood Installation

VentingEach furnace must be connected to a venting system to convey flue gases outside of the heated space. Refer to in-stallation codes noted above fo

Page 23 - VCES-VHC72-IOM-1H

NomenclatureThe VHC-72 offers a wide range of features and options and can be used as a stand alone air-to-air energy recovery device or as an integra

Page 24 - IMPORTANT

3. The vent system must also be installed to prevent collection of condensate. Pitch horizontal pipe runs downward ¼” per foot [21 mm per meter] towa

Page 25

Proper installation of combustion air intake and flue gas exhaust piping are essential to proper operation of the in-shot gas burner module. See Figure

Page 26 - Flow Equation

4. For the furnace(s) to operate properly, the minimum inlet gas supply pressure to each furnace for natural gas operation is 5.0” w.c. and for propa

Page 27 - Installation and Maintenance

3. The heat capacity of the furnace is controlled by the burner orifices and the gas manifold pressure. The manifold pressure is factory set but shoul

Page 28 - Indoor Installation

Operating and Safety Instructions1. See Figure D8 for component locations.2. This furnace module does not have a pilot. It is equipped with a direct

Page 29

may be caused by lint and dirt accumulation inside burner or at burner ports, at air inlet be-tween burner and manifold pipe, or debris in the main bu

Page 30

2. The furnace is equipped with manual reset rollout switch(es) in the event of burner flame rollout. The switch will open on temperature rise and shu

Page 31

On/Off Burner Firing Rate Control with Utec 1016-xxx Direct Spark IgnitionSequence of Operation1. Thermostat closes on call for heat providing 24 VAC

Page 32

Two-stage Burner Firing Rate Control with Utec 1171-63 Direct Spark IgnitionSequence of OperationWhen the control is in standby mode, the diagnostic r

Page 33

Table D4: Troubleshooting Guide for Utec 1171-63 Two-stage BoardLED CodeSystem ModeDescription ActionsHeartbeat System is functioning properly. None2

Page 34 - WARNING – FOR YOUR SAFETY

Safety ConsiderationsWarning, Caution and Important notes appear throughout this manual in specific and appropriate locations to alert Installing Contr

Page 35 - Security Device Operation

Full Modulation Burner Firing Rate Control with Utec 1016-427 Direct Ignition Control, TR1 Timer and SC30 Modulating ControlSequence of Operation1. T

Page 36 - Furnace Module Inspection

Table D5: Troubleshooting Guide for Utec 1016-xxx Ignition BoardLED CodeSystem ModeDescription ActionsSteady On Normal LED is lit. 24 VAC is applied t

Page 37

This page intentionally left blank.VCES-VHC72-IOM-1H42

Page 38 - Sequence of Operation

Appendix E: VHC-72 Start-up Form and ChecklistTable D1: Pre Start-up ChecklistChecklist Item Yes N/A1 Is the electrical disconnect set to the ‘Off’ po

Page 39

Table E2: Start-up ChecklistChecklist Item Yes N/A1 Before proceeding complete the Pre Start-up Checklist.2 Close all access panels or doors.3 Turn th

Page 40

Serial Number: _____________________________________Table E3: Start-up ReadingsMode of Operation Heating CoolingPower supplyNameplate voltageVoltage a

Page 41

This unit has been checked out and started according with the above procedures and completed forms and is operat-ing satisfactorily.After 24 hours of

Page 42

Appendix F: HEPA Filter InstallationThese instructions are for installing AAF HEPA filters (11½” depth) into AAF HEPA holding frames. The holding frame

Page 43

Step 2Insert the HEPA filter into the HEPA holding frame. The HEPA should be installed with the gasket side of the filter facing the frame. Insert the fi

Page 44 - Table E2: Start-up Checklist

Step 4Once all four corner latches have been tightened within ¼” of the leg extension coupling, complete the installation by tightening each corner un

Page 45 - Table E3: Start-up Readings

Unit Inspection on ArrivalInspect the equipment exterior and interior for any dam-age on arrival that may have occurred during unit ship-ment and for

Page 46

Appendix G: Electric Heating Coil and Controls InformationThis electric heating coil module covered by this appen-dix is a component of a “Listed” pro

Page 47

3 – Operating Electric Coil Heaters3.1 Minimum AirflowEnsure that sufficient airflow as marked on the nameplate is passing through the heater. Airflow sho

Page 48

Appendix H: TroubleshootingTable H1: VHC-72 TroubleshootingProblem Cause SolutionUnit will not turn on.Occupancy contact open.Check internal time cloc

Page 49

VCES-VHC72-IOM-1G53Table H1: VHC-72 TroubleshootingProblem Cause SolutionCompressor runs but stops quickly.Overload, fuse burnout.Check if voltage is

Page 50

Appendix I: Enthalpy Wheel Pressure Drop vs. Flow Formula and CurvesEnthalpy Wheel Pressure Drop vs. Flow FormulaFlow in cfm = pressure drop measured

Page 51 - 4 – Maintenance

Appendix J: Enthalpy Wheel Multi-link Drive Belt InstructionsHow to MeasurePull belt tight around sheaves to check hand tight length, overlapping the

Page 52 - Appendix H: Troubleshooting

Alternative Installation Method1. Set motor in mid position of adjustment range and mark base clearly.2. Determine required belt length as described

Page 53 - VCES-VHC72-IOM-1G

Appendix K: FANWALL® Supply Fan Inlet Cone AlignmentNote: Drawings not to scale4.280Blade width(100% wide)0.7000.250 overlap12.500O.D.backplateWheel/C

Page 54 - Flow Formula and Curves

Appendix L: Forward Curved Exhaust Fan Bearing Relubrication ScheduleFan Model ATL1 9-6 & ATL1 9-7 ATL1 10-7 & ATL1 10-9 ATL1 12-9 ATL1 12-12

Page 55 - Installation

Appendix M: VHC-72 Maintenance Summary ChartTable M1: VHC-72 Maintenance SummaryItem No. Description Note Monthly QuarterlySemi-annuallyAnnuallyGenera

Page 56 - Retensioning

InstallationUnit Location RequirementsConsult local building codes and electrical codes for spe-cial installation requirements and note additional req

Page 57 - Appendix K: FANWALL

IMPORTANTFor gas-fired furnace module maintenance, see Appendix D and for electric coil maintenance, see Appendix G.Table M1: VHC-72 Maintenance Summar

Page 58 - Relubrication Schedule

©2012 Venmar CESVCES-VHC72-IOM-1H (PN 5000044944)September 2014Venmar CES has a policy of continuous improvement and reserves the right to change desi

Page 59

Roofcurbs Supplied by Venmar CES (External Applications Only)Roofcurbs supplied by Venmar CES should be mounted as follows:• The roofcurb is shipped

Page 60

Rigging and Lifting the UnitUnit shall be lifted by cables attached to all the lifting lugs provided on the unit base. Consult the mechanical draw-ing

Page 61

Internal PackagingOpen access doors or panels and remove all packaging from the unit. Removal of all packaging is critical.Electrical ConnectionsThe u

Commentaires sur ces manuels

Pas de commentaire