VCES-DDC-IOM-1C
10
WSHP Heating, One Compressor, Optional VRC
®
(Discharge Air Temperature Control)
If outside air temperature is below summer setpoint (se-
lectable), and if coil leaving air temperature rises above
heating setpoint (selectable), first compressor starts. Mod-
ulate compressor to heating setpoint. Additional postheat
will heat up supply air if heating setpoint cannot be main-
tained (if equipped).
WSHP Heating, Two Compressors, or Two-stage
Single Compressor (Discharge Air Temperature
Control)
If outside air temperature is below summer setpoint (se-
lectable), and if supply air temperature rises above heat-
ing setpoint (selectable), first compressor starts. If more
heating is needed based on heating setpoint, after staging
delay, second compressor starts. Additional postheat will
heat up supply air if heating setpoint cannot be main-
tained (if equipped).
WSHP Heating, Two Compressors, First
Compressor VRC (Discharge Air Temperature
Control)
If outside air temperature is below summer setpoint (se-
lectable), and if coil leaving air temperature rises above
heating setpoint (selectable), first compressor starts and
modulates to maintain setpoint. If more cooling is needed
based on heating setpoint, after staging delay, second
compressor starts. The first compressor will continue to
modulate to maintain coil leaving air temperature. Addi-
tional postheat will heat up supply air if heating setpoint
cannot be maintained (if equipped).
WSHP Heating, One Compressor, Optional VRC
(Room Air Temperature Control)
If outside air temperature is below summer setpoint (ad-
justable), and if (return) room air temperature drops below
winter zone setpoint and coil leaving air temperature is
below heating setpoint, first compressor starts. Compres-
sor modulates to coil leaving air setpoint (adjustable). This
continues until (return) room air temperature is satisfied.
Additional post heat will heat up supply air if heating set-
point cannot be maintained (if equipped).
WSHP Heating, Two Compressors, or Two-stage
Single Compressor (Room Air Temperature Control)
If outside air temperature is below summer setpoint (se-
lectable), and if (return) room air temperature rises above
winter zone setpoint and coil leaving air is above heating
setpoint, first compressor starts. If more cooling needed
based on heating setpoint, after staging delay second
compressor starts. This continues until (return) room air
temperature is satisfied. Additional post heat will heat
up supply air if heating setpoint cannot be maintained (if
equipped).
WSHP Heating, Two Compressors, First
Compressor VRC (Room Air Temperature Control)
If outside air temperature is below summer setpoint (se-
lectable), and if (return) room air temperature rises above
winter zone setpoint and coil leaving air is above heating
setpoint, first compressor starts and modulates to main-
tain setpoint. If more cooling is needed based on heating
setpoint, after staging delay, second compressor starts.
The first compressor will continue to modulate to maintain
coil leaving air temperature. Additional post heat will heat
up supply air if heating setpoint cannot be maintained (if
equipped).
WSHP Economizer Coil
If the outside air temperature is above summer setpoint
(adjustable) and if the water entering temperature is
below the economizer coil setpoint (adjustable) the econo-
mizer coil valve will modulate to maintain the coil leaving
air temperature. If the economizer coil valve is open 100%
for more than two minutes, then the mechanical cooling
will be allowed to stage on. The economizer coil valve will
remain open while in mechanical cooling until the water
entering temperature is above the economizer coil set-
point (adjustable).
With both the economizer coil and free cooling options, if
the outside air temperature is above summer setpoint and
is in the free cooling range, then the economizer coil valve
will close and temperature control will follow free cooling.
If the outside air temperature rises above the free cooling
range and the water entering temperature is below the
economizer setpoint (adjustable) then the economizer coil
valve will modulate and mechanical cooling will stage on
to maintain the coil leaving air temperature as above.
WSHP Freeze Protection
If the unit has a water leaving temperature sensor and this
temperature goes below the water leaving temperature
setpoint (adjustable) then the compressor is locked off and
the WSHP valve is opened.
WSHP Head Pressure Control
If the outside air temperature is above the summer set-
point (adjustable) and there is the demand for mechani-
cal cooling, the head pressure control valve will open to
100%. When the compressor starts, the valve will modu-
late to maintain the factory set head pressure setpoint.
The valve will be allowed to close to a minimum valve
setpoint of 50%. If the compressor has been off for 10
minutes then the valve will close.
If the outside air temperature is below the summer set-
point (adjustable) and there is a demand for mechanical
heating, the head pressure control valve will open fully
and remain open until the compressor has been off for 10
minutes.