VCES-DDC-IOM-1C
12
The middle characters represent the mode the unit is in:
‘Un’ = Unoccupied.
‘Ov’ = Occupied ventilation.
‘Or’ = Occupied recirculation.
‘Ur’ = Unoccupied recirculation.
The bottom characters represent the supply air cooling/
heating setpoint. If the zone configuration is set to dis-
charge air control (MV11= NO) and the unit has hot gas
reheat, then this will display the cooling setpoint in sum-
mer mode and the heating setpoint in the winter mode. If
the unit does not have hot gas reheat then it will display
the coil leaving setpoint in the summer mode. If the zone
configuration is set to room or return air (MV11= RM or
RET) then this will display the summer zone setpoint in the
summer mode and the winter zone setpoint in the winter
mode.
To navigate through the setpoints, use the on and off
buttons—on to go up, off to go down. To change the set-
points, use the up and down arrow buttons. Push once on
the up button to go up, push it again to stop. See Appen-
dix B for the entire read and read/write variables.
Supply air
temperature/
maintenanc
e
Mode
Heating/cooling
icon
Supply air
setpoint
Supply fan
on icon
Figure 5: Main screen
Item number
Description
Setpoint
Figure 6: Changing setpoints
Vue de la page 11